6 System Commissioning and Functions NICE3000
new
User Manual
- 136 -
◆
Independent Running
The independent running function is described as follows:
●
The elevator responds to only car calls; it does not respond to hall calls, and the registered hall
call is cleared automatically.
●
The elevator does not close the door automatically. You need to hold down the door close button
to close the door. During door close, if you release the door close button, the elevator opens the
door again automatically.
●
If the elevator is under parallel/group control, it exits the parallel/group control system after
entering the independent running state.
●
Set FE-32 Bit9 to 1, and perform independent running signal input via JP23 on the MCTC-
CCB-A.
◆
Fire Emergency Running
The re emergency function is described as follows:
●
The elevator clears car calls and hall calls automatically.
●
The elevator stops at the nearest oor without opening the door, and then directly runs to the re
emergency oor.
●
The elevator keeps the door open after arriving at the re emergency oor.
●
If the elevator is under parallel/group control, it exits the parallel/group control system after
entering the re emergency running state.
Note that the preceding description is the default setting of the system, and certain actions can be modied
by setting the related parameters.
The reghter function is described as follows:
●
The elevator does not respond to hall calls. It responds to only the car call and only one car call
can be registered.
●
The elevator does not open or close the door automatically. You need to press the door open/
close button (jog) to open/close the door.
●
The light curtain signal input is inactive, and the safety edge signal input is active.
Note that the preceding description is the default setting of the system, and certain actions can be modied
by setting the related parameters.
The input and output setting of re emergency running and reghter running is as follows:
1. Input setting:
● Generally, the re emergency signal is input via the re emergency switch on the HCB of
any oor, and the reghter signal is input via JP24 on the CCB. If these signals need to be
input via the MCB, perform parameter setting (takes input terminal Xa and Xb as an example)
according to the following table.