6 System Commissioning and Functions
- 137 -
● The NICE3000
new
supports switchover between two re emergency oors, and the switchover
signal is input via the MCB (take input terminal Xc as an example).
2. Output setting:
The re emergency oor arrival signal is output via output terminal Y on the MCB (take Y3 as an
example).
The parameter setting related to re emergency running and reghter running is described in the
following table.
Function Code Parameter Name Value
F5-a Xa function selection
11: NO re emergency signal
43: NC re emergency signal
F5-b Xb function selection
23: NO reghter running signal
55: NC reghter running signal
F5-c Xc function selection
72: NO re emergency oor switchover signal
104: NC re emergency oor switchover signal
F5-28 Y3 function selection 4: Fire emergency oor arrival signal
The other parameters related to re emergency running and reghter running are listed in the
following table.
Function Code Parameter Name Setting Range Default
F6-03
Fire emergency
oor 1
F6-01 to F6-00 1
F6-44
Fire emergency
function selection
Bit3: Arrival gong output in inspection or re emergency state
Bit4: Multiple car calls registered in re emergency state
Bit5: Retentive at power failure in re emergency state
Bit6: Closing door by holding down the door close button
Bit8: Door close at car call registering
Bit9: Displaying hall calls in re emergency state
Bit10: Fireghter forced running
Bit11: Exiting reghter state upon arrival at re emergency
oor
Bit12: Not clearing car calls at reverse door open in
reghter running state
Bit14: Opening door by holding down the door open button
Bit15: Automatic door open at re emergency oor
16456
F8-12
Fire emergency
oor 2
0 to F6-00 0
For detailed descriptions of these parameters, refer to Chapter 8.