EasyManua.ls Logo

Monarch nice3000 - Page 157

Monarch nice3000
322 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6 System Commissioning and Functions NICE3000
new
User Manual
- 156 -
6
3. Use description of parallel control
Denition of oors:
User oor: actual oor of the building
Physical oor: oor which either elevator stops at and provides service for or oor installed with
the leveling plate.
For the same physical oor, the leveling plate must be installed for both the elevators. Even if
one elevator need not stop at a certain oor, the leveling plate must be installed at this oor for
this elevator. You can set the service oors of this elevator so that it does not stop at this oor.
The HCB addresses should be set according to physical oors. Parallel running can be
implemented only when the HCB address set for one elevator is the same as that for the other
elevator in terms of the same oor.
The top oor (F6-00) and bottom oor (F6-01) of each elevator should be set based on the
corresponding physical oors of this elevator.
Example:
Assume that there are two elevators in parallel mode:
Elevator 1# has one underground user oor and four overground user oors, but stops only at oor
B1, oor 1, oor 2, and oor 3.
Elevator 2# has four overground user oors ,but stops only at oor 1, oor 3, and oor 4.
Figure 6-23 Floor diagram of two elevators in parallel control
4
3
2
1
5
4
2
Elevator 1#
Elevator 2#
Physical floor 5
Floor B1
Floor 1
Floor 2
Floor 3
5
Leveling plate
HCB address
User floor
Floor 4
(Not stop)
Floor 4 Floor 4
Floor 3
Floor 2
Floor 1
Physical floor 4
Physical floor 3
Physical floor 2
Physical floor 1

Table of Contents

Related product manuals