7 Function Code Table NICE3000
new
User Manual
- 186 -
Function
Code
Parameter Name Setting Range Default Unit Property Page
Fd-09 HCB:JP1 output
0: Invalid
1: Up arrival indicator
2: Down arrival indicator
3: Fault output
4: Non-door zone stop output
5: Non-service state output
6: Door close button indicator
output
1 -
★
250
Fd-10 HCB:JP2 output 2 -
★
250
Fd-11 HCB-B:JP1 input
0: Reserved
NO/NC input:
1/33: Light-load signal
2/34: Half-load signal
3/35: Door 2 selection
4/36: Door 2 restricted (back door
forbidden)
5/37: Door 1 safety edge
6/38: Door 2 safety edge
7/39: Single/Double door selection
0 -
★
250
Fd-12 HCB-B:JP2 input 0 -
★
250
Fd-13 HCB-B:JP3 input 0 -
★
250
Fd-14 HCB-B:JP4 input 0 -
★
250
Fd-15 HCB-B:JP5 input 0 -
★
250
Fd-16 HCB-B:JP6 input 0 -
★
250
Fd-17 HCB-B:A1 output
0: Reserved
1: Fault output
2: Non-door zone stop output
3: Non-service state output
4: Fire emergency output
5: Power failure emergency output
6: Door lock valid
7: Night output signal
0 -
★
250
Fd-18 HCB-B:A2 output 0 -
★
250
Fd-19 HCB-B:B1 output 0 -
★
250
Fd-20 HCB-B:B2 output 0 -
★
250
Fd-21 HCB-B:C1 output 0 -
★
250
Fd-22 HCB-B:C2 output 0 -
★
250
Fd-23 HCB-B:C3 output 0 -
★
Fd-24 HCB-B:C4 output 0 -
★
250
Fd-25 HCB-B:C5 output 0 -
★
250
Fd-26 HCB-B:C6 output 0 -
★
Group FE: Elevator function parameters
FE-00
Collective selective
mode
0: Full collective selective
1: Down collective selective
2: Up collective selective
0 -
★
216
FE-01 Floor 1 display The two high digits indicate the
display code of the ten's digit,
and the two low digits indicate the
display code of the unit's digit.
00: Display "0"
01: Display "1"
02: Display "2"
03: Display "3"
04: Display "4"
(To be continued)
1901 -
☆
251
FE-02 Floor 2 display 1902 -
☆
251