APPENDIX D – CX-Server Error Codes OMRON
Page 306 Release 2.0
0xnn0E The open PLC handle specified is invalid.
0xnn0F The open Project handle specified is invalid.
0xnn10 The open User handle specified is invalid.
0xnn11 The Key specified is invalid or cannot be found.
0xnn12 The device or function is locked by another user or application.
0xnn13 The name specified does not exist or cannot be found.
0xnn14 The specified PLC name does not exist.
0xnn15 The specified Project cannot be found or created.
0xnn16 The operation cannot be performed as the correct access permissions have not be
obtained. This usually indicates another host currently has the PLC access rights.
0xnn17 The function or CDMPLCCommand is not supported in this version of CX-Server.
0xnn18 The PLC could not be opened or the operation failed because the PLC is open for
communications. Check the communication settings and that another application is not
currently using the connection method e.g Mouse configured and using COM1 port.
0xnn19 The Point could not be opened or the operation failed because the Point is open for
communications.
0xnn1A Attempt to delete a currently selected User.
0xnn1B Communications to the device could not be established or the connection has been
broken. Check the communication settings and connection method to the device.
0xnn1C An executing command was aborted by the execution of another command or action.
0xnn1D CX-Server is currently processing the maximum number of requests. This error
indicates the application is thrashing the maximum possible communications
throughput of the device's connection.
0xnn1E CX-Server has reached the maximum limitation for the specified function.
0xnn1F Communications Error occurred because of a Network Routing Table problem. Check
the routing tables in all devices are correctly configured. In Alpha C series PLC's ensure
the 'Allow Routing Table' flag is set.
0xnn20 The specified Point name or key is invalid.
0xnn21 Device setup information or settings configuration is incorrect.
0xnn22 Device configuration information or data is incorrect.
0xnn23 The Unit number specified is invalid or does not exist.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron CX-SUPERVISOR - V2.0 and is the answer not in the manual?

Omron CX-SUPERVISOR - V2.0 Specifications

General IconGeneral
BrandOmron
ModelCX-SUPERVISOR - V2.0
CategorySoftware
LanguageEnglish

Related product manuals