• Set
the upper limit and lower limit of the output frequency in 1% units based on the maximum
frequen
-
cy set with n012 as 100%.
• The
Inverter will operate at the lower limit of the output frequency set with n031 if the frequency refer
-
ence
used by the Inverter is set to 0.
The Inverter will not, however
, operate if n031 is set to a value
smaller than the minimum output frequency set with n017.
Internal frequency
reference
Output frequency
upper limit (n030)
Output frequency
lower limit (n031)
Set frequency reference
n032 Motor Rated Current
Setting range 10% to 200% of
rated output
current of In-
verter
Unit A Default setting See note
Note The default-set value varies with the Inverter model. Refer to the following table.
Set Values
• Set
the rated input current of the motor to determine electronic thermal protection characteristics for
the motor.
• The
parameter n032 is set to
the rated input current of the maximum applicable motor before shipping.