3-82
Select with n051 a method to process instantaneous power failure.
Set Values
Set value Description
0 Inverter will discontinue running.
1 Inverter will continue running if power is supplied again within instantaneous power failure
compensation time set with n055. (see note 1)
2 Inverter will always continue running without detecting UV1 or UV3. (see notes 1 and 2)
Note 1. Keep the run command ON to permit the Inverter to restart operation automatically when
power is supplied to the Inverter after the operation of the Inverter is interrupted due to an
instantaneous power failure.
Note 2. If
n051 is set to 2, the Inverter will restart running after supply voltage to the Inverter returns to
normal and the Inverter will not detect error output signals.
n052 Speed Search Control Level
Setting range 0 to 200 Unit % (Rated output
current ratio)
Default setting 110
Set
with n052 a current level in
1% units based on the rated output current as 100% which enables the
Inverter to determine the completion of the speed search control.
It is usually not necessary to change the default-set value.
To
permit the Inverter to use the speed search function, set the multi-function input parameter used by
the Inverter to 15 or 16 so that the speed search command will be input to the Inverter.
When
the output
current becomes less than the value set with n054, the Inverter in speed search con
-
trol will detect the synchronous speed and the Inverter will be in acceleration mode.
n053 Minimum Baseblock Time
Setting range 0.5 to 10.0 Unit s Default setting See note
Note The default-set value varies with the Inverter model.
Set
with n053 time in 1-s units to start the speed search control after RUN
input is ON and instanta
-
neous power failure processing starts. Refer to
page 3-70, Speed Search Command
.
n054 V/f Characteristics During Speed Search
Setting range 0 to 100 Unit % (Usual V/f
characteristics
ratio)
Default setting See note
Note The default-set value varies with the Inverter model.
Set percentage of V/f characteristics for speed search.
It is usually not necessary to change the default-set value.
n055 Stop Compensation Time
Setting range 0.0 to 2.0 Unit s Default setting See note
Note The default-set value varies with the Inverter model.
Preparing for Operation Chapter 3

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron SYSDRIVE 3G3HV SERIES and is the answer not in the manual?

Omron SYSDRIVE 3G3HV SERIES Specifications

General IconGeneral
BrandOmron
ModelSYSDRIVE 3G3HV SERIES
CategoryInverter
LanguageEnglish

Related product manuals