3-26
The
most ef
ficient input voltage imposed on the motor varies with the load factor of the motor
. The In
-
verter
in energy-saving mode calculates the ideal output voltage and adjusts
the ideal output voltage so
that the actual power supplied to the motor can be minimized.
Power
consumption
Load factor: 100%
Motor voltage
Load factor: 50%
H Energy-saving Control Settings
n095 Energy-saving Control Selection
Setting range 0, 1 Unit --- Default setting 0
Set Values
Set value Description
0 Inhibits the Inverter from performing energy-saving control.
1 Permits the Inverter to perform energy-saving control.
Note Set n095 to 1 so that the Inverter will perform energy-saving control.
n096 Energy-saving Coefficient K2
Setting range 0.00 to 655.0 Unit --- Default setting See note
Note The default-set value of n096 varies with the Inverter model.
Set Values
S Set the K2 value according to the capacity of the motor.
S The
K2 value of each Inverter model is set to the following before shipping according to the maxi
-
mum capacity of the motor that can be connected to the Inverter model.
Preparing for Operation Chapter 3

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron SYSDRIVE 3G3HV SERIES and is the answer not in the manual?

Omron SYSDRIVE 3G3HV SERIES Specifications

General IconGeneral
BrandOmron
ModelSYSDRIVE 3G3HV SERIES
CategoryInverter
LanguageEnglish

Related product manuals