3-26
The
most ef
ficient input voltage imposed on the motor varies with the load factor of the motor
. The In
-
verter
in energy-saving mode calculates the ideal output voltage and adjusts
the ideal output voltage so
that the actual power supplied to the motor can be minimized.
Power
consumption
Load factor: 100%
Motor voltage
Load factor: 50%
H Energy-saving Control Settings
n095 Energy-saving Control Selection
Setting range 0, 1 Unit --- Default setting 0
Set Values
Set value Description
0 Inhibits the Inverter from performing energy-saving control.
1 Permits the Inverter to perform energy-saving control.
Note Set n095 to 1 so that the Inverter will perform energy-saving control.
n096 Energy-saving Coefficient K2
Setting range 0.00 to 655.0 Unit --- Default setting See note
Note The default-set value of n096 varies with the Inverter model.
Set Values
S Set the K2 value according to the capacity of the motor.
S The
K2 value of each Inverter model is set to the following before shipping according to the maxi
-
mum capacity of the motor that can be connected to the Inverter model.
Preparing for Operation Chapter 3