EasyManua.ls Logo

Omron SYSDRIVE 3G3HV SERIES

Omron SYSDRIVE 3G3HV SERIES
207 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
3-26
The
most ef
ficient input voltage imposed on the motor varies with the load factor of the motor
. The In
-
verter
in energy-saving mode calculates the ideal output voltage and adjusts
the ideal output voltage so
that the actual power supplied to the motor can be minimized.
Power
consumption
Load factor: 100%
Motor voltage
Load factor: 50%
H Energy-saving Control Settings
n095 Energy-saving Control Selection
Setting range 0, 1 Unit --- Default setting 0
Set Values
Set value Description
0 Inhibits the Inverter from performing energy-saving control.
1 Permits the Inverter to perform energy-saving control.
Note Set n095 to 1 so that the Inverter will perform energy-saving control.
n096 Energy-saving Coefficient K2
Setting range 0.00 to 655.0 Unit --- Default setting See note
Note The default-set value of n096 varies with the Inverter model.
Set Values
S Set the K2 value according to the capacity of the motor.
S The
K2 value of each Inverter model is set to the following before shipping according to the maxi
-
mum capacity of the motor that can be connected to the Inverter model.
Preparing for Operation Chapter 3

Table of Contents

Related product manuals