3-88
The parameters n074, n075, and n076 are used to set the overtorque detection function.
Select
with n074 whether to permit the
Inverter to detect overtorque and a method to process the over
-
torque.
The
Inverter will detect overtorque if the output current as large as or larger
than the detection level set
with n075 flows for a period as long as or longer than the detection time set with n076.
Set
with n075 an overtorque detection current level in
1% units based on the rated output current as
100%.
Set with n076 overtorque detection time in 1-s units.
Refer to
page 3-77
to permit the Inverter to output an overtorque detection signal as multi-function
contact output.
Set Values (n074)
Set value Description
0 Inhibits Inverter from detecting overtorque.
1 Inverter will detect overtorque only during speed agreement and continue running with a
warning after detection.
2 Running Inverter will detect overtorque and continue running with a warning after detection.
3 Inverter will detect overtorque only during speed agreement and turn OFF output for safety
when overtorque is detected.
4 Running Inverter will always detect overtorque and turn OFF output for safety when overtorque
is detected.
n077 Timer Function ON Delay Time
Setting range 0.0 to 25.5 Unit s Default setting 0.0
n078 Timer Function OFF Delay Time
Setting range 0.0 to 25.5 Unit s Default setting 0.0
The parameters n077 and n078 are used to set the timer function.
To
permit the Inverter to use the timer function, set the multi-function input parameter used by the In
-
verter
to 20 for timer function input and the multi-function contact output parameter used by the Invert
-
er to 11 for timer function output.
Set
with n077 delay time in1-s units to permit the Inverter to turn ON timer function
output after timer
function input is ON.
Set
with n078 delay time in 1-s units to permit the Inverter to turn OFF timer function output after timer
function input is OFF.
Refer to
page 3-71, Timer Function Input (Set Value = 20)
for the timer function in detail.
n079 Braking Resistor Overheating Protection Selection
Setting range 0, 1 Unit --- Default setting 0
Preparing for Operation Chapter 3

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron SYSDRIVE 3G3HV SERIES and is the answer not in the manual?

Omron SYSDRIVE 3G3HV SERIES Specifications

General IconGeneral
BrandOmron
ModelSYSDRIVE 3G3HV SERIES
CategoryInverter
LanguageEnglish

Related product manuals