XtraDrive User Manual Chapter 2: Installation
2-4
Servo Amplifier Orientation
Install the servo amplifier perpendicular to the wall so the front panels’
connectors faces outward.
Cooling
As shown in the figure above, allow sufficient space around each servo
amplifier for cooling by cooling fans or natural convection.
Side-by-side Installation
When installing servo amplifiers side by side as shown in the figure
above, allow at least 0.39in (10mm) between and at least 1.97in
(50mm) above and below each servo amplifier. Install cooling fans
above the servo amplifiers to avoid excessive temperature rise and to
maintain even temperature inside the control panel.
Environmental Conditions in the Control Panel
• Ambient Temperature: 0 to 55°C
• Humidity: 90% RH or less
• Vibration: 0.5 G (4.9m/s
2
)
• Condensation and Freezing: None
• Ambient Temperature for Long-term Reliability: 45°C max.