XtraDrive User Manual Appendix B: Special Wiring
B-4
MCCB or Fuse According to Power Capacity
The following table shows the MCCB or fuse capacity for each power
supply capacity.
Servo Amplifier
Model
Main Circuit
Power
Supply
Capacity
(kW)
XD-
Applicable
Motor
Power
Capacity per
Servo
Amplifier
(kVA)*
Current
Capacity per
MCCB or
Fuse(A
rms
)*
**
0.05 P5 SGMAH-A5A 0.25
SGMAH-01A
0.10 01
SGMPH-01A
0.40
SGMAH-02A
0.20 02
SGMPH-02A
0.75
4
SGMAH-04A
0.40 04
SGMPH-04A
1.2 8
SGMAH-08A
0.75 08
SGMPH-08A
2.1 11
Single-phase
200V
1.50 15 SGMPH-15A 4.0 19
SGMGH-09D
SGMSH-10D
1.0 10
SGMUH-10D
2.3 3.4
SGMGH-09D
Three-phase
400V
2.0 20
SGMSH-10D
4.9 7.1
* This is the net value at the rated load. When actually selecting fuses, determine the capacity using the prescribed
derating.
** Operating characteristics (at 25°C): 2 seconds or more for 200%, 0.01 second or more for 700%
Note: 1. A fast-operating fuse cannot be used because the servo amplifier power supply is a capacitor input
type. A fast-operating fuse may blow when the power is turned ON.
2. XtraDrive servo amplifiers do not have built-in ground protection circuits. To configure a safer
system, install a ground fault interrupter with or without a circuit breaker for protection against
overload and short circuit conditions.

Table of Contents

Other manuals for Omron XTRADRIVE

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron XTRADRIVE and is the answer not in the manual?

Omron XTRADRIVE Specifications

General IconGeneral
BrandOmron
ModelXTRADRIVE
CategoryComputer Hardware
LanguageEnglish

Related product manuals