2
Site Requirements
This chapter describes the site requirements for the Exalogic machine.
This chapter contains the following topics:
Environmental Requirements
Space Requirements
Flooring Requirements
Electrical Power Requirements
Temperature and Humidity Requirements
Ventilation and Cooling Requirements
See Also:
Site Checklists
2.1 Environmental Requirements
The environmental requirements for an Exalogic machine depend on the purchased
hardware configuration. The environmental requirements for an Exalogic rack can be
found in the data sheets at the following location:
http://www.oracle.com/technetwork/server-storage/engineered-
systems/exalogic/index.html
2.2 Space Requirements
All Exalogic machines use the same rack, and have the same space requirements. The
space requirements are as follows:
Height: 1998 mm (78.66 inches)
Width: 600 mm with side panels (23.62 inches)
Depth (front door handle to rear door handle): 1200 mm (47.24 inches)
Depth (doors removed): 1112 mm (43.78 inches)
The minimum ceiling height for the cabinet is 2300 mm (90 inches), measured from the
true floor or raised floor, whichever is higher. An additional 914 mm (36 inches) is for
top clearance. The space above the cabinet and its surroundings must not restrict the
movement of cool air between the air conditioner and the cabinet, or the movement of
hot air coming out of the top of the cabinet.