The following checklist is specific to the power distribution units (PDUs) when using
the reracking service.
PDU Reracking Considerations Yes No N/A Comment
Does the target rack support
installation of standard Oracle PDUs?
If not, then complete this checklist.
Can the customer provide an
equivalent pair of PDUs?
Can the customer provide two PDUs
with capacity of 10kVA per PDU?
Can the customer provide at least the
following number of 10A C13 plugs
per PDU:
• Half rack: 46 cables
• Quarter rack: 28 cables
• Eighth rack: 20 cables
Can the customer provide a single
PDU and its circuits to support the
power requirements in case one PDU
fails?
Can the customer ensure power loads
are evenly distributed across all
circuits of a single PDU?
Can the customer provide
appropriate power drops for the
PDUs?
B.10.1 Rack Recycling
The following checklist is specific to recycling the rack:
Recycling Considerations
Yes No N/A Comment
Does the customer want Oracle to
take back and recycle the empty rack?
If yes, then the shipping company can
pack the empty rack for recycling.
If Oracle is recycling the rack, then
has the customer completed the
appropriate application at the Oracle
Electronic Waste and Product Return
website?
The website is at
http://www.oracle.com/us/
products/applications/green/
waste-and-product-
returns-185031.html
Reracking Checklists
B-12 Oracle Exalogic Elastic Cloud Machine Owner's Guide

Table of Contents