Table 2-4 lists the PDU low voltage requirements.
Table 2-4 PDU Requirements for Low Voltage
Specification 15 kVA, 1 ph 15 kVA, 3 ph 22 kVA, 1 ph 24 kVA, 3 ph
Phase 1 ph 3 ph 1 ph 3 ph
Market Part
Number
6442A 6440A 7100873 XSR-24K-IEC309-4P
Manufacturing
Part Number
597-0566-01 597-0564-01 7018123 594-5596-01
Voltage 200-240 VAC 1ph 200-240 VAC 3ph 200-240 VAC 1ph 200-240 VAC 3ph
Amps Per PDU 72A (3 × 24A) 69A (3 × 23A) 110.4 (3x36.8A) 120A (6 × 20A)
Outlets 42 C13, 6 C19 42 C13, 6 C19 42 C13, 6 C19 42 C13, 6 C19
Number of
Inputs
3x30A, 1 ph 1x60A, 3 ph 3 x50A 1 ph 2x60A, 3 ph
Current 24A max. per
input
40A max. per phase 36.8A per input 34.6A max. per phase
Data Center
Receptacle
NEMA L6-30R IEC309-3P4W-IP67
(60A, 250V, AC, 3 ph)
IEC309 60A 3ph 4 Wire
Hubbell
HBL460R/C9W or
equivalent.
Hubbell CS8265C IEC309-3P4W-IP67
(60A, 250V, AC, 3 ph)
IEC309 60A 3ph 4
Wire
Hubbell
HBL460R/C9W or
equivalent.
Number of
Outlets Per Rack
6 2 6 4
Table 2-5 lists the PDU high voltage requirements.
Table 2-5 PDU Requirements for High Voltage
Specification 15 kVA, 3 ph 22 kVA, 1 ph 24 kVA, 3 ph
Phase 3 ph 1 ph 3 ph
Market Part Number 6441A 7100874 XSR-24K-IEC309-5P
Manufacturing Part
Number
597-0565-01 7018124 594-5600-01
Voltage 220/380-240/415 VAC 3ph 200-240 VAC 1ph 220/380-240/415 VAC
3ph
Amps Per PDU 62.7 A (3 × 20.9A) 96A (3x32A) 109A (6 × 18.1A)
Outlets 42 C13, 6 C19 42 C13, 6 C19 42 C13, 6 C19
Number of Inputs 1x25A, 3 ph 3 x 32A 1 ph 2x25A, 3 ph
Electrical Power Requirements
2-4 Oracle Exalogic Elastic Cloud Machine Owner's Guide