R9036
F152 (RMRD)/P152
(PRMRD) and F153
(RMWT)/P153
(PRMWT) instruction
end flag
Monitors if an abnormality has been detected during the
execution of the F152 (RMRD)/P152 (PRMRD) and F153
(RMWT)/P153 (PRMWT) instructions as follows:
- off: No abnormality detected.
- on: An abnormality detected. (access error)
The error code is stored in DT90036.
R9037
COM port communica-
tion error flag
Turns on when the serial data communication error occurs
using COM port.
Turns off when data is being sent by the F144 (TRNS)
instruction.
R9038 COM port receive flag
Turns on when the end code is received during the serial
R9039 COM port send flag
Turns on while data is not sent during the serial data
communicating.
Turns off while data is being sent during the serial data
communicating.
-
R9040
Error alarm (0 to 2047)
Available PLC:
Turns on while the error alarm relay (E0 to E2047) acts.
Turns off when the all error alarm relay turns off.