Because RFL™ and Hubbell® have a policy of continuous product improvement, we reserve the right to change designs and specifications without notice.
RFL VF-5C RFL Electronics Inc.
October 8, 2012 40 (973) 334-3100
Table 6. continued - Remote configuration settings (“P” codes)
P Code Digit(s) And Switch Equivalent Value
(1)
Description
P7
B 0 0 0 0 0 0 0 0
↑ - - - - - - -
0 (+) Positive
CH2 TRANSMIT LEVEL SIGN
1 (-) Negative
B 0 0 0 0 0 0 0 0
- ↑ ↑ ↑ ↑ ↑ ↑ -
From
000000
to 101110
Range is from –23dB to +10dB
Resolution is 0.5dB. For example +7dB = 001110,
CH2 TRANSMIT LEVEL
and set sign to (+). For example –16dB = 100000,
and set sign to (-).
B 0 0 0 0 0 0 0 0
- - - - - - - ↑
0 Ch2 Signaling Disabled
CH2 SIGNALING ENABLE
1 Ch2 Signaling Enabled
P8
B 0 0 0 0 0 0 0 0
↑ - - - - - - -
0 (+) Positive
CH2 RECEIVE LEVEL SIGN
1 (-) Negative
B 0 0 0 0 0 0 0 0
- ↑ ↑ ↑ ↑ ↑ ↑ -
From
000000
to 101100
Range is from –22dB to +10dB
Resolution is 0.5dB. For example +7dB = 001110,
CH2 RECEIVE LEVEL
and set sign to (+). For example –16dB = 100000,
and set sign to (-).
B 0 0 0 0 0 0 0 0
- - - - - - - ↑
0 Ch2 Not Busy
CH2 BUSY
1 Ch2 Busy
P9
B 0 0 0 0 0 0 0 0
↑ ↑ ↑ ↑ ↑ ↑ ↑ -
CH2 TRANSMIT ADDRESS
From
0000000
To 1111111
0 = 0000000
127 = 1111111
See description of addressing for more details.
B 0 0 0 0 0 0 0 0
- - - - - - - ↑
0 Ch2 Addressing Disabled
CH2 ADDRESSING ENABLE
1 Ch2 Addressing Enabled
P10
B 0 0 0 0 0 0 0 0
↑ ↑ ↑ ↑ ↑ ↑ ↑ -
CH2 RECEIVE ADDRESS
From
0000000
To 1111111
0 = 0000000
127 = 1111111
See description of addressing for more details.
B 0 0 0 0 0 0 0 0
- - - - - - - ↑
0 Ch2 FX Mode Disabled
CH2 FX MODE ENABLE
1 Ch2 FX Mode Enabled