Because RFL and Hubbell® have a policy of continuous product improvement, we reserve the right to change designs and specications without notice.
RFL DS-TT RFL Electronics Inc.
January 31, 2008 31 (973)
334-3100
TRANSFER TRIP SPECIFIC SCL COMMANDS
The SCL commands in this section are specific to the RFL DS-TT Transfer Trip module and are
related to the sequence of events log.
There are three types of occurrences that qualify as “events” in the sequence of events log. These are;
input trip, output trip and alarm conditions. There are three types of alarm conditions; received address
error, CRC error, or ping-pong exceeded preset limit. If any of these events occurrs, it will be entered
into the sequence of events log with a date stamp (month, day, year) and time stamp (hours, minutes,
seconds).
Up to twenty events can be stored in the sequence of events log. Instructions on how to access the
sequence of events log, and how to program the time and date stamp is discussed below.
TIME? Command
In order to read the time and date setting of an RFL DS-TT module do the following: For example, if
the module is channel 3 in shelf number 2,
INPUT: 2:C3:TIME?:;
RESPONSE: *OK
FROM NET ADDRESS = 2
CHANNEL CARD 3, TYPE 118
DATE = 10-12-92
TIME = 13 Hrs.: 15 Mins.: 12 Secs.;
EVENT
In order to read one of the twenty sequence of events occurrences, do the following:
INPUT: 2:C3:EVENT:20;
RESPONSE: *OK
FROM NET ADDERSS = 2
CHANNEL CARD 3, TYPE 118
EVENT NUMBER 20
DATE = 10-12-92
TIME = 13 Hrs.: 15 Mins.: 12 Secs.: 034 ms.
OUTPUT #4 ACTIVE
INPUT #2 ACTIVE
ADDRESS SIGNAL ERROR ACTIVE
CRC ERROR ACTIVE
PING PONG IS 0 ms.;