RFL Electronics Application Note AN2000-019
Motherboard
Power Supply I/O
Alarm Configuration
Module installed
Plan View of IMUX 2000 Chassis (typical)
J1
J2
1
32
NORMAL
TPU-ALERT
TPU-ALARM
NORMAL
Alarm Configuration Module
Figure 1. Alarm Configuration Module with Jumper positions
There are two failure situations that can occur:
A. An internal system failure as detected by the Common Module.
B. A loss of signal condition (TPU).
Jumpers J1 and J2 configure the module as follows:
Jumper Position Result
J1 Normal
J2 Normal
Alarm/Alert relays on. (default). I/O is driven by failure conditions
in
ternal to the system, as detected by the Common Module.
J1 Normal
J2 TPU-Alarm
As above; but additional alarm contacts are driven by the TPU (loss of
si
gnal condition).
J1 TPU-Alert
J2 Normal
As above; but additional alert contacts are driven by the TPU (loss of
si
gnal condition).