Rockwell Automation Publication 193-UM015D-EN-P - February 2015 417
EtherNet/IP Communications Chapter 9
7. To access the data provided by the E300 Electronic Overload Relay
EtherNet/IP Communication Module, navigate to input tags created by
the Generic Profile.
Table 498 represents the Input Assembly data.
Table 498 - Instance 199 - Input (Produced) Assembly
Bit
INT DINT1514131211109876543210
0
0 Reserved for Logix
1
2
1
DeviceStaus0
3
DeviceStaus1
4
2
InputStatus0
5
InputStatus1
6
3
OutputStatus
7
OpStationStatus
8
4
TripStsCurrent
9
WarnStsCurrent
10
5
Tri pStsVo lt age
11
WarnStsVoltage
12
6
Tri pStsPower
13
WarnStsPower
14
7
TripStsCo ntrol
15
WarnStsControl
16
8
TripStsAna log
17
WarnStsAnalog
18
9Reserved
19
20
10
ThermUtilizedPct
CurrentImbalance
21
AvgPercentFLA
22
11 AverageCurrent
23
24
12 L1Current
25
26
13 L2Current
27
28
14 L3Current
29
30
15
GFCurrent
31
Reserved
32
16
AvgVoltageLtoL
33
L1toL2Voltage
34
17
L2toL3Voltage
35
L3toL1Voltage