486 Rockwell Automation Publication 193-UM015D-EN-P - November 2013
Appendix B Parameter List
Power Setup 377 PowerScale C.PowerScale Power value scale
factor (kW MW)
USINT 1 1 0=kW
1=MW
0
378 UWInhibitTime C.UnderRealPowerInhibitTime Under Total Real
Power Inhibit Time
USINT 1 1 0 250 10
Second
s
379 UWTripDelay C.UnderRealPowerTripDelay Under Total Real
Power Trip Delay
USINT 1 10 1 250 10
Second
s
380 UWTripLevel C.UnderRealPowerTripLimit Under Total Real
Power Trip Level
DINT 4 1000 0 2000000000 0 kW
381 UWWarningLevel C.UnderRealPowerWarnLimit Under Total Real
Power Warning
Level
DINT 4 1000 0 2000000000 0 kW
382 OWInhibitTime C.OverRealPowerInhibitTime Over Total Real
Power Inhibit Time
USINT 1 1 0 250 10
Second
s
383 OWTripDelay C.OverRealPowerTripDelay Over Total Real
Power Trip Delay
USINT 1 10 1 250 10
Second
s
384 OWTripLevel C.OverRealPowerTripLimit Over Total Real
Power Trip Level
DINT 4 1000 0 2000000000 0 kW
385 OWWarningLevel C.OverRealPowerWarnLimit Over Total Real
Power Warning
Level
DINT 4 1000 0 2000000000 0 kW
386 UVARCInhibitTime C.UnderReactivePowerConsumedInhibitTime Under Total
Reactive Power
Consumed
(+kVAR) Inhibit
Time
USINT 1 1 0 250 10
Second
s
387 UVARCTripDelay C.UnderReactivePowerConsumedTripDelay Under Total
Reactive Power
Consumed
(+kVAR) Trip Delay
USINT 1 10 1 250 10
Second
s
388 UVARCTripLevel C.UnderReactivePowerConsumedTripLimit Under Total
Reactive Power
Consumed
(+kVAR) Trip Level
DINT 4 1000 0 2000000000 0 kVAR
389 UVARCWarnLevel C.UnderReactivePowerConsumedWarnLimit Under Total
Reactive Power
Consumed
(+kVAR) Warning
Level
DINT 4 1000 0 2000000000 0 kVAR
390 OVARCInhibitTime C.OverReactivePowerConsumedInhibitTime Over Total Reactive
Power Consumed
(+kVAR) Inhibit
Time
USINT 1 1 0 250 10
Second
s
391 OVARCTripDelay C.OverReactivePowerConsumedTripDelay Over Total Reactive
Power Consumed
(+kVAR) Trip Delay
USINT 1 10 1 250 10
Second
s
Group
Param
No.
Parameter Name Device Profile Tag Name Description Type
Data Size
(bytes)
Scale
Factor
Min Max Default Units