R.6.45
Date Code 20111215 Reference Manual SEL-421 Relay
DNP3 Communications
DNP LAN/WAN Documentation
30 4
e
16-Bit Analog Input
Without Flag
1 0, 1, 6, 7,
8, 17, 28
129 0, 1,
17, 28
30 5 Short Floating Point
Analog Input
1 0, 1, 6, 7,
8, 17, 28
129 0, 1,
17, 28
30 6 Long Floating Point
Analog Input
1 0, 1, 6, 7,
8, 17, 28
129 0, 1,
17, 28
31 0 Frozen Analog Input—
All Variations
31 1 32-Bit Frozen Analog
Input
31 2 16-Bit Frozen Analog
Input
31 3 32-Bit Frozen Analog
Input With Time of
Freeze
31 4 16-Bit Frozen Analog
Input With Time of
Freeze
31 5 32-Bit Frozen Analog
Input Without Flag
31 6 16-Bit Frozen Analog
Input Without Flag
32 0 Analog Change Event—
All Variations
1 6, 7, 8
32 1 32-Bit Analog Change
Event Without Time
1 6, 7, 8 129 17, 28
32 2
e
16-Bit Analog Change
Event Without Time
1 6, 7, 8 129, 130 17, 28
32 3 32-Bit Analog Change
Event With Time
1 6, 7, 8 129 17, 28
32 4 16-Bit Analog Change
Event With Time
1 6, 7, 8 129 17, 28
32 5 Short Floating Point
Analog Change Event
1 6, 7, 8 129 17, 28
32 6 Long Floating Point
Analog Change Event
1 6, 7, 8 129 17, 28
33 0 Frozen Analog Event—
All Variations
33 1 32-Bit Frozen Analog
Event Without Time
33 2 16-Bit Frozen Analog
Event Without Time
33 3 32-Bit Frozen Analog
Event With Time
33 4 16-Bit Frozen Analog
Event With Time
Tabl e 6 . 24 SEL -421 DNP3 Object List (Sheet 4 of 6)
Obj. Var. Description
Request
a
Response
b
Funct.
Codes
c
Qual.
Codes
d
Funct.
Codes
c
Qual.
Codes
d