SEL-421 Relay Reference Manual Date Code 20111215
Synchrophasors
C37.118 Synchrophasor Protocol
The SEL-421 will only respond to configuration block request messages when
it is in the non-transmitting mode.
Independent Ports
Each serial port with the PROTO := PMU setting is independently configured
and enabled for synchrophasor and Fast Operate commands. For example, if
there are two serial ports set to PROTO := PMU, the status of one port has no
effect on the other port. One port might be commanded to start transmitting
synchrophasor messages, while the other port is idle, responding to a
configuration block or Fast Operate request, or transmitting synchrophasors.
The ports are not required to have the same SPEED setting, although the
slowest SPEED setting on a PROTO := PMU port will affect the maximum
Global MRATE setting that can be used.
PMU Setting Example
A power utility is upgrading the line protection on its 230 kV system to use
the SEL-421 Relay as main protection. The grid operator also wants the utility
to install phasor measurement units (PMUs) in each 230 kV substation to
collect data for a new remedial action scheme, and to eventually replace their
present state-estimation system.
The PMU data collection requirements call for the following data, collected at
10 messages per second:
Frequency
Positive-sequence voltage from the bus in each substation
Three-phase and positive-sequence current for each line
terminal
Indication when the line breaker is open
Indication when the voltage or frequency information is
unusable
Ambient temperature (one reading per station)
Station battery voltage
No relay control from the PMU communications port, for the
initial stage of the project
The utility is able to meet the grid operator requirements with the SEL-421, an
SEL-2600A RTD Module, an SEL-2407 Satellite Synchronized Clock, and an
SEL-3306 Synchrophasor Processor in each substation.
This example will cover the PMU settings in one of the SEL-421 relays.
Some system details:
The nominal frequency is 60 Hz.
The line is protected by a breaker-and-a-half scheme (similar to
Figure 1.7 on page R.1.10).
The station ambient temperature is collected by an SEL-2600A,
channel RTD01.
The line pts and wiring have a phase error of 4.20 degrees
(lagging) at 60 Hz.
The breaker 1 cts and wiring have a phase error of 3.50 degrees
(lagging) at 60 Hz.