R.8.11
Date Code 20111215 Reference Manual SEL-421 Relay
IEC 61850 Communications
IEC 61850 Operation
Every received and validated GOOSE message that indicates a
data change, by an incremented status number, is evaluated as
follows:
Data within the received GOOSE dataset that are
mapped to host data bits are identified.
Mapped bits are compared against a local version of the
available host data bits.
If the state of the received bits is different than the local
version,
Update the local version with the new state for
that bit.
Pass the new state for the bit to the SEL-421.
Reject all DA contained in an incoming GOOSE based on the
accumulation of the following error indications created by
inspection of the received GOOSE:
Configuration Mismatch. The configuration number
of the incoming GOOSE changes.
Needs Commissioning. This Boolean parameter of the
incoming GOOSE is true.
Test Mode. This Boolean parameter of the incoming
GOOSE is true.
Decode Error. The format of the incoming GOOSE is
not as configured.
The SEL-421 will discard incoming GOOSE under the
following conditions:
after a permanent (latching) self-test failure
when the host is not responding
when EGSE is set to No
Link-layer priority tagging and virtual LAN is supported as described in
Annex C of IEC 61850-8-1:2004(E).
GOOSE Performance
For outgoing high-speed data (CCOUTn data, as identified under GOOSE
Processing on page R.8.10), transmission of GOOSE begins within 2 ms of
transition of data within the SEL-421. For all other data contained in outgoing
GOOSE, transmission of GOOSE begins within 500 ms of transition of data
within the SEL-421. Appropriate control commands are issued to the
SEL-421 within 2 ms of a GOOSE reception.