Configuring the fieldbus
7.2 Communication via PROFIBUS
Inverter with CU230P-2 Control Units
Operating Instructions, 11/2013, FW V4.6.6, A5E02430659B AG
115
The following telegrams are available:
p0015
Macro drive unit
Configure the interface in basic commissioning, and select a telegram.
p0922
PROFIdrive Telegram selection
Set the send and receive telegram, also see Cyclic communication (Page 116)
1:
20:
350:
352
353:
354:
Standard telegram 1, PZD-2/2 (factory setting)
Standard telegram 20, PZD-2/6
SIEMENS telegram 350, PZD-4/4
SIEMENS telegram 352, PZD-6/6
SIEMENS telegram 353, PZD-2/2, PKW-4/4
SIEMENS telegram 354, PZD-6/6, PKW-4/4
Extend telegrams and change signal interconnection (Page 123)
In the basic commissioning, you have selected a setting with fieldbus.
See also Section: Basic commissioning (Page 80).
Proceed as follows to set a specific telegram in the inverter:
Using STARTER or an operator panel, set parameter p0922 to the appropriate value.
You have set a specific telegram in the inverter.