EasyManua.ls Logo

Siemens SINAMICS G120 - General Data, PM230 - IP20

Siemens SINAMICS G120
456 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Technical data
12.2 Technical data, Power Modules
Inverter with CU230P-2 Control Units
Operating Instructions, 11/2013, FW V4.6.6, A5E02430659B AG
377
12.2.1.1
General data, PM230 - IP20
Feature
Version
Line voltage
380 V ... 480 V 3-ph. AC ± 10%
Output voltage
0 V 3-ph. AC … input voltage x 0.95 (max.)
Input frequency
50 Hz … 60 Hz, ±3 Hz
Output frequency
0 … 650 Hz, depending on the control mode
Power factor λ
0.9
Line impedance
Uk ≤ 1%, no line reactor permitted
Starting current
Less than the input current
Pulse frequency (factory
setting)
4 kHz
The pulse frequency can be increased in 2 kHz steps up to 16 kHz (up to 8 kHz for 55 kW
and 75 kW). An increase in the pulse frequency results in a lower output current.
Electromagnetic
compatibility
Devices with filters in compliance with EN 61800-3: 2004 are suitable for Category C2
environments. For details, see the Hardware Installation Manual, Appendix A2.
Braking methods
DC braking
Degree of protection IP20 built-in units
PT devices
IP20 when mounted in a control cabinet
IP54 on the control cabinet wall
Operating temperature LO without power reduction:
HO without power reduction:
LO/HO with power reduction:
0 °C … +40 °C
0 °C … +50 °C
to 60 °C
For details, see the Hardware
Installation Manual.
Storage temperature
-40 °C … +70 °C
Relative humidity
< 95% - condensation not permissible
Contamination
Protected according to pollution degree 2 to EN 61800-5-1: 2007
Environmental requirements Protected against damaging chemical substances according to environmental class 3C2 to
EN 60721-3-3; 1995
Shock and vibration
Long-term storage in the transport packaging according to Class 1M2 to EN 60721-3-1:
1997
Transport in the transport packaging according to Class 2M3 to EN 60721-3-2: 1997
Vibration during operation according to Class 3M2 to EN 60721-3-3: 1995
Installation altitude without power reduction:
with power reduction:
up to 1000 m above sea level
up to 4000 m above sea level
For details, see the Hardware
Installation Manual
Permissible short-circuit
current
Frame size D ... F: 65 kA
1)
Overvoltage category Supply circuits:
Non-supply circuits:
Overvoltage category III
Overvoltage category II
Standards UL
1),2)
, CE, C-tick
The drive only satisfies the UL requirements when UL-certified fuses are used.
1)
If fuse-protected with a listed Class J or 3NE1 fuse, rated voltage 600 VAC with the rated current of the specific
converter.
2)
UL available soon for frame sizes D … F

Table of Contents

Other manuals for Siemens SINAMICS G120

Related product manuals