Setting functions
8.6 Protection functions
Inverter with CU230P-2 Control Units
Operating Instructions, 11/2013, FW V4.6.6, A5E02430659B AG
261
8.6.2
Motor temperature monitoring using a temperature sensor
Connecting the temperature sensor
You can use one of the following sensors to protect the motor against overtemperature:
Temperature switch (e.g. bimetallic switch)
PTC sensor
KTY84 sensor
Connect the temperature sensor of the motor to terminals
14 and 15 of
the inverter.
Set response to excess motor temperature
If you use a temperature switch or PTC sensor, set the response to excess motor
temperature via P0610 as follows:
p0610 = 0
Warning A07910,
No shutdown
p0610 = 1, p0610 = 2, p0610 = 12
Warning A07910
Shutdown with fault F07011
If you use a KTY84 sensor, set the temperature for the warning or fault threshold via p0604
or p0605.
Monitoring via p0604: Response as per the setting in p0610
Monitoring via p0605: Shutdown with fault as soon as the set threshold is exceeded.
For details, please refer to the List Manual.
Temperature switch
The inverter interprets a resistance ≥ 100 Ω as being an opened temperature switch and
responds according to the setting for p0610.
PTC sensor
The inverter interprets a resistance > 1650 Ω as being an overtemperature and responds
according to the setting for p0610.
The inverter interprets a resistance < 20 Ω as being a short-circuit and responds with alarm
A07015. If the alarm is present for longer than 100 milliseconds, the inverter shuts down with
fault F07016.