Technical data
12.2 Technical data, Power Modules
Inverter with CU230P-2 Control Units
Operating Instructions, 11/2013, FW V4.6.6, A5E02430659B AG
407
12.2.6
PM330 technical data
Permissible inverter overload
The inverters have different load capabilities, "High Overload" and "Low Overload",
depending on the expected.
Figure 12-6 Load cycles, Low Overload" and "High Overload"
12.2.6.1
PM330 general data
Table 12- 42 General technical data
Electrical data
Line system configurations
Grounded TN/TT systems and non-grounded IT systems
Line requirement
A line reactor (2% u
k
) must be connected in series
Line voltage
380 V (-10%) ... 480 V (+10%)
Line frequency
47 ... 63 Hz
Output frequency
0 ... 100 Hz
Displacement factor cos φ
power factor λ
0.96
0.75 ... 0.93 (with line reactor u
k
= 2%)
Inverter efficiency
> 98%
Short-circuit current rating
per IEC, in conjunction with
the specified fuses
110 ... 200 kW: 100 kA
Short-circuit current rating
per UL508C (up to
480 VAC), in conjunction
with the specified fuses
110 ... 200 kW: 100 kA
Can be used on supply systems that cannot supply more than 100 kA symmetrically for a
maximum voltage of 480 VAC when they are protected with the listed fuses of type Class J
or approved semi-conductor fuses specified in the "Technical Data" section of this manual.
Overvoltage category
III according to EN 61800-5-1
Mechanical data
Degree of protection IP20
Protection class
according to EN 61800-5-1: Class I (with protective conductor system) and Class III (PELV)
Cooling method
Forced air cooling AF according to EN 60146
Sound pressure level L
PA
(1 ma)
≤ 71 dB(A)
Touch protection
according to EN 61800-5-1: For the intended purpose