Technical data
12.2 Technical data, Power Modules
Inverter with CU230P-2 Control Units
378 Operating Instructions, 11/2013, FW V4.6.6, A5E02430659B AG
Power-dependent data, PM230, IP20
Note
For the PM230 Power Modules, IP20, the low
overload values (LO) are identical to the rated
Table 12- 1 PM230, IP20, Frame Sizes A, 3 AC 380 V … 480 V
Order No. - without filter
Order No. - with filter
LO power
LO input current
0.37 kW
1.3 A
0.55 kW
1.8 A
0.75 kW
2.3 A
HO power
HO input current
0.25 kW
0.9 A
0.37 kW
1.3 A
0.55 kW
1.8 A
Fuse according to IEC
3NE1 813-0
3NE1 813-0
3NE1 813-0
Power loss 0.04 kW 0.04 kW 0.05 kW
Required cooling air flow 1.5 l/s 1.5 l/s 4.5 l/s
Cross section of line and motor cables 1 … 2.5 mm
2
1 … 2.5 mm
2
1 … 2.5 mm
2
Tightening torque for line and motor cables
Weight, unfiltered
1.4 kg
1.4 kg
1.4 kg
Table 12- 2 PM230, IP20, Frame Sizes A, 3 AC 380 V … 480 V
Order No. - without filter
Order No. - with filter
…-1NE15-8UL0
…-1NE15-8AL0
LO power
LO input current
1.1 kW
3.2 A
1.5 kW
4.2 A
2.2 kW
6.1 A
HO power
HO input current
0.75 kW
2.3 A
1.1 kW
3.2 A
1.5 kW
4.2 A
Fuse according to IEC
3NE1 813-0
3NE1 813-0
3NE1 813-0
Required cooling air flow
Cross section of line and motor cables 1 … 2.5 mm
2
1 … 2.5 mm
2
1.5 … 2.5 mm
2
Tightening torque for line and motor cables
Weight, unfiltered
1.4 kg
1.4 kg
1.4 kg