Installing
4.3 Installing Power Modules
Inverter with CU230P-2 Control Units
Operating Instructions, 11/2013, FW V4.6.6, A5E02430659B AG
45
4.3.1
Dimensions, hole drilling templates, minimum clearances, tightening torques
Dimensions and drilling patterns for the PM230 Power Modules, IP55
Table 4- 1 Dimensions and clearances for the PM230, IP55
Frame
size
Dimensions (mm)
Clearances (mm)
Height
Width
Depth
a
b
top
bottom
lateral
FSA
460
154
238
445
132
100
100
0
FSB
540
180
238
524
158
100
100
0
FSC
620
230
238
604
208
125
125
0
FSD
640
320
238
600
285
300
300
0
FSE
751
320
238
710
285
300
300
0
FSF
915
410
238
870
370
300
300
0
Table 4- 2 Mounting hardware for the PM230, IP55
Frame size
Material
Tightening torque
FSA, FSB
M4 screws
2.5 Nm
FSC
M5 screws
2.5 Nm
FSD, FSE, FSF
M8 screws
13 Nm