Technical data
12.2 Technical data, Power Modules
Inverter with CU230P-2 Control Units
Operating Instructions, 11/2013, FW V4.6.6, A5E02430659B AG
397
Power-dependent data PM240-2
Table 12- 29 PM240-2, IP20, Frame Sizes A, 3 AC 380 V … 480 V
Order No. - without filter
Order No. - with filter
LO power
LO input current
0.55 kW
2.3 A
0.75 kW
2.9 A
1.1 kW
4.1 A
HO power
HO input current
0.37 kW
2.0 A
0.55 kW
2.6 A
0.75 kW
3.3 A
Fuse according to IEC
3NA3 804 (4 A)
3NA3 804 (4 A)
3NA3 801 (6 A)
Power losses without filter
0.04 kW
0.04 kW
0.04 kW
Required cooling air flow
Cross section of line and motor cables 1 … 2.5 mm
2
1 … 2.5 mm
2
1 … 2.5 mm
2
Tightening torque for line and motor cables
Weight without filter
1.4 kg
1.4 kg
1.4 kg
Table 12- 30 PM240-2, IP20, Frame Sizes A, 3 AC 380 V … 480 V
Order No. - without filter
Order No. - with filter
LO power
LO input current
LO output current
1.5 kW
5.5 A
4.1 A
2.2 kW
7.7 A
5.9 A
3.0 kW
10.1 A
7.7 A
HO power
HO input current
1.1 kW
4.7 A
1.5 kW
6.1 A
2.2 kW
8.8 A
Fuse according to IEC
3NA3 803 (10 A)
3NA3 803 (10 A)
3NA3 805 (16 A)
Power losses without filter
0.07 kW
0.1 kW
0.12 kW
Required cooling air flow
Cross section of line and motor cables 1 … 2.5 mm
2
1.5 … 2.5 mm
2
1.5 … 2.5 mm
2
Tightening torque for line and motor cables
Weight without filter
1.4 kg
1.4 kg
1.4 kg