Installing
4.5 Connecting inverters in compliance with EMC
Inverter with CU230P-2 Control Units
68 Operating Instructions, 11/2013, FW V4.6.6, A5E02430659B AG
4.5.2
Avoid electromagnetic interference (EMI)
The inverters are designed to operate in an industrial environment where a high level of EMI
can be expected. Safe, reliable and disturbance-free operation is only guaranteed if the
devices are professionally installed.
Control cabinet design
Connect the metal parts and components of the control cabinet to the control cabinet
frame through a good electrical connection:
Side panels
Rear panels
Roof
Base plates
Using the highest possible surface area or a high number of individual screw
connections.
Connect the PE bar and the EMC shield bar to the control cabinet frame through a good
electrical connection established through a large surface area.
Connect the metal enclosures of the devices in the cabinet, e.g. converter or line filter, to
the control cabinet frame through a good electrical connection through the largest
possible surface area.
We recommend to mount these devices on a bare metal mounting plate with good
conducting characteristics.
Choose one of the following methods to establish a conducting contact for screw
connections on painted or anodized surfaces:
Use special contact (serrated) washers that cut through the
Remove the insulating surface at the contact locations
Equip the following devices with interference suppression elements:
Coils of contactors
Relays
Solenoid valves
Motor holding brakes
Interference suppression elements are RC elements or varistors with AC coils and free-
wheeling diodes or varistors for DC coils.
Connect the interference suppression elements directly at the coil.