Technical data
12.2 Technical data, Power Modules
Inverter with CU230P-2 Control Units
Operating Instructions, 11/2013, FW V4.6.6, A5E02430659B AG
375
12.2
Technical data, Power Modules
Definitions
LO input current
100% of the permissible input current for a load cycle according to
Low Overload (LO base load input current).
LO output current
100% of the permissible output current for a load cycle according
to Low Overload (LO base load output current).
LO power
Power of the inverter for LO output current.
HO input current
100% of the permissible input current for a load cycle accordi
ng to
High Overload (HO base load input current).
HO output current
100% of the permissible output current for a load cycle according
to High Overload (HO base load output current).
HO power
Power of the inverter for HO output current.
If the power data comprises rated values without any further specifications they always refer
to an overload capability corresponding to Low Overload.
Note
The base load (100% power or current) of "Low Overload" is greater than the base load of
"High Overload".
We recommend the "SIZER" engineering software to select the inverter based on duty
cycles.
See Manuals for your inverter (Page 446).