Setting functions
8.4 Setpoint calculation
Inverter with CU230P-2 Control Units
244 Operating Instructions, 11/2013, FW V4.6.6, A5E02430659B AG
8.4
Setpoint calculation
8.4.1
Overview of setpoint processing
The setpoint can be modified as follows using the setpoint processing:
Invert setpoint to reverse the motor direction of rotation (reversing).
Inhibit positive or negative direction of rotation, e.g. for conveyor belts, pumps or fans.
Minimum speed to avoid standstill when the motor is switched on.
Limit to a maximum speed to protect the motor and mechanical system.
Ramp-function generator to accelerate and brake the motor with an optimum torque.
Figure 8-18 Setpoint processing in the inverter
8.4.2
Invert setpoint
Procedure
Proceed as follows to invert the setpoint:
Interconnect parameter p1113 with
a binary signal,
e.g. digital input 1.
You have inverted the setpoint.
Table 8- 15 Examples of settings to invert the setpoint
Parameter
Remark
p1113 = 722.1
Setpoint inversion
Digital input 1 = 0: Setpoint remains unchanged.
Digital input 1 = 1: Inverter inverts the setpoint.
p1113 = 2090.11
Invert setpoint via control word 1, bit 11.