Corrective maintenance
10.7 Correcting an unsuccessful firmware upgrade or downgrade
Inverter with CU230P-2 Control Units
352 Operating Instructions, 11/2013, FW V4.6.6, A5E02430659B AG
10.7
Correcting an unsuccessful firmware upgrade or downgrade
How does the inverter signal an unsuccessful upgrade or downgrade?
The inverter signals an unsuccessful firmware upgrade or
downgrade by a quickly flashing LED RDY and the lit LED BF.
Correcting an unsuccessful upgrade or downgrade
You can check the following to correct an unsuccessful firmware upgrade or downgrade:
Does the firmware version of your inverter fulfill the preconditions?
For an upgrade, as a minimum V4.5.
For a downgrade, as a minimum V4.6.
Have you correctly inserted the card?
Does the card contain the correct firmware?
Repeat the appropriate procedure.