Setting functions
8.4 Setpoint calculation
Inverter with CU230P-2 Control Units
Operating Instructions, 11/2013, FW V4.6.6, A5E02430659B AG
245
8.4.3
Enable direction of rotation
In the factory setting of the inverter, the negative direction of rotation of the motor is inhibited.
Procedure
Proceed as follows to permanently enable the negative direction of rotation:
Set parameter p1110 to a value = 0.
You have permanently enabled the negative direction of rotation.
Table 8- 16 Examples of settings to inhibit the direction of rotation
Parameter
Remark
p1110 = 1
Inhibit negative direction
Negative direction is permanently inhibited.
p1110 = 722.3
Inhibit negative direction
Digital input 3 = 0: Negative direction of rotation is enabled.
Digital input 3 = 1: Negative direction of rotation is inhibited.
8.4.4
Minimum speed
The inverter prevents continuous motor operation
at speeds <
minimum speed.
Speeds, where the absolute value is less than the
minimum speed, are only possible when
accelerating or braking.
Table 8- 17 Setting the minimum speed
Parameter
Description
p1080
Minimum speed