Commissioning
5.4 Basic commissioning
Inverter with CU230P-2 Control Units
Operating Instructions, 11/2013, FW V4.6.6, A5E02430659B AG
89
Carry-out basic commissioning
Configuring the drive
Procedure
Proceed as follows to carry out basic commissioning:
See also Section: U/f control or speed control? (Page 250)
Select the default setting of the inverter interfaces.
Selecting the pre-assignment for the terminal strip
Select the application for the inverter:
Low overload for applications that only require a low dynamic
performance, e.g. pumps or fans.
High overload for applications requiring a high dynamic performance,
e.g. conveyor systems.
Enter the motor data according to the rating plate of your motor.
ve selected a motor based on its order number, the data has
If you have set the "Speed control" control mode, then we recommend
setting "[1] Identify motor data at standstill and with motor rotating".
With this setting, the
inverter optimizes its speed
controller.
If one of the following cases is applicable, select the setting "[2]
Identify
motor data at standstill":
You have selected "Speed control" as control mode, however the
motor cannot freely rotate, e.g. for mechanically limited traversing
sections.
You have set "V/f control" as control mode.
Set the most important parameters to suit your application.
We recommend the
setting "Calculate
motor data only".
Set the check mark for "RAM to ROM (save data
in the drive)" in order to save your data in the
inverter so that it is not lost when the power fails.
Exit basic commissioning.
You have entered all of the data that is necessary for the basic commissioning of your
inverter.