Technical data
12.2 Technical data, Power Modules
Inverter with CU230P-2 Control Units
Operating Instructions, 11/2013, FW V4.6.6, A5E02430659B AG
395
Table 12- 28 PM240 frame sizes GX, 3 AC 380 V … 480 V
Order No. - without filter
Values for rated load/low overload
Rated/LO power
Rated/LO input current
160 kW
297 A
200 kW
354 A
240 kW
442 A
HO power
HO input current
132 kW
245 A
160 kW
297 A
200 kW
354 A
Fuse according to IEC
Fuse according to UL (from SIEMENS)
3NA3254
3NA3260
3NA3372
Required cooling air flow
Cross section of line and motor cables 95 ... 2 x 240 mm
2
120 ... 2 x 240 mm
2
185 ... 2 x 240 mm
2
Tightening torque for line and motor cables
Technical data, PM240-2
12.2.3.1
High overload - low overload PM240-2
Permissible inverter overload
The inverters have different load capabilities, "High Overload" and "Low Overload",
depending on the expected.
Figure 12-3 Load cycles, Low Overload" and "High Overload"