Setting functions
8.7 Application-specific functions
Inverter with CU230P-2 Control Units
296 Operating Instructions, 11/2013, FW V4.6.6, A5E02430659B AG
8.7.10
Time switch (DTC)
The "time switch" (DTC) function, along with the real time clock in the inverter, offers the
option of controlling when signals are switched on and off.
Examples:
Switching temperature control from day to night mode.
Switching a process control from weekday to weekend.
Principle of operation of the time switch (DTC)
The inverter has three independently adjustable time switches. The time switch output can
be interconnected with every binector input of your inverter, e.g. with a digital output or a
technology controller's enable signal.
Figure 8-31 Time behavior of the time switch using example DTC1
Setting the time switch
Enable parameterization of the DTC: p8409 = 0.
As long as DTC parameterization is enabled, the inverter keeps the output of all three
DTC (r84x3, x = 1, 2, 3) at LOW.
Set the activation of the weekdays; the switching on and off times.
Enable the setting: p8409 = 1.
The inverter enables the DTC output once more.
Additional information is provided in the parameter list of the List Manual.