Configuring the fieldbus
7.3 PROFIdrive profile for PROFIBUS and PROFINET
Inverter with CU230P-2 Control Units
Operating Instructions, 11/2013, FW V4.6.6, A5E02430659B AG
129
Write request: Assign digital input 2 with the function ON/OFF1 (p0840[1] = 722.2)
In order to link digital input 2 with OFF1/ON, you must assign parameter p0840[1] (source,
ON/OFF1) the value 722.2 (DI 2). To do this, you must fill the telegram of the parameter
channel as follows:
PKE, bit 12 … 15 (AK): = 7 hex
(change, parameter value (field, word))
PKE, bit 0 … 10 (PNU): = 348 hex
(840 = 348 hex, no offset, as 840 < 1999)
IND bit 815 (subindex): = 1 hex
(CDS1 = index1)
IND, bit 07 (page index): = 0 hex
(offset 0
0 hex)
PWE1, bit 015
: =
2D2 hex
(722 = 2D2 hex)
PWE2, bit 1015: = 3f hex
(drive object - for SINAMICS G120, always 63 = 3f hex)
PWE2, bit 09: = 2 hex
(index of parameter (DI 2 = 2))
Figure 7-7 Telegram, to assign DI 2 with ON/OFF1
"Reading and writing parameters" application example
See: Reading and writing parameters via PROFIBUS
(http://support.automation.siemens.com/WW/view/en/8894584
).
7.3.1.5
Slave-to-slave communication
"Direct data exchange" is sometimes called "slave-to-slave communication" or "data
exchange broadcast". Here, slaves exchange data without any direct involvement of the
master.
Example: An inverter uses the actual speed value of another inverter as its speed setpoint.
Definitions
Publisher:
Slave, which sends data for direct data exchange.
Subscriber:
Slave, which receives the data for direct data exchange from the publisher.
Links and access points
define the data that is used for direct data exchange.
Restrictions
Direct data exchange in the current firmware version is only possible for inverters with
PROFIBUS communication.
A maximum of 12 PZDs are permissible for each drive.
To a publisher, a maximum of 4 links are possible.