Technical data
12.2 Technical data, Power Modules
Inverter with CU230P-2 Control Units
384 Operating Instructions, 11/2013, FW V4.6.6, A5E02430659B AG
General data, PM230, IP55
380°V°...°480°V 3-ph.°AC ±°10%
0 V 3-ph. AC … input voltage x 0.95 (max.)
0 … 650 Hz, depending on the control mode
Uk ≤ 1%, no line reactor permitted
Less than the input current
Pulse frequency (factory
setting)
4 kHz
The pulse frequency can be increased in 2 kHz steps up to 16 kHz (up to 8 kHz for 75kW
and 90kW). An increase in the pulse frequency results in a lower output current.
Electromagnetic
The devices comply with EN 61800-3: 2004 suitable for Category C1 and C2 environments.
For details, see the Hardware Installation Manual, Appendix A2
Degree of protection FSA … FSC IP55 / UL Type 12
FSD … FSF IP55 / UL Type 12 in preparation
Note: For the end cover plate, you must use the relevant bolting plates for the cable glands
and the corresponding cable glands and seals to achieve the degree of protection UP55 (UL
type 12).
Degree of protection IP54 / UL Type 12 is reached if an IOP is inserted.
Operating temperature without power reduction:
0 °C … +40 °C
For details, see the Hardware
< 95% - condensation not permissible
Protected from contact with dangerous parts, dust, spray water and water jets
Environmental requirements Protected against damaging chemical substances according to environmental class 3C2 to
Shock and vibration
• Long-term storage in the transport packaging according to Class 1M2 to EN 60721-3-1:
1997
• Transport in the transport packaging according to Class 2M3 to EN 60721-3-2: 1997
• Vibration during operation according to Class 3M2 to EN 60721-3-3: 1995
Installation altitude without power reduction:
up to 1000 m above sea level
up to 4000 m above sea level
For details, see the Hardware
Permissible short-circuit
Frame sizes A ... C: 40 kA
1)
Frame sizes D ... F: 65 kA
1)
Standards UL
2)
, CE, C-tick
The drive only satisfies the UL requirements when UL-certified fuses are used.
If fuse-protected with a listed Class J fuse, rated voltage 600 VAC with the rated current of the specific converter.
2)
UL available soon for frame sizes D … F