Configuring the fieldbus
7.5 Communication via EtherNet/IP
Inverter with CU230P-2 Control Units
Operating Instructions, 11/2013, FW V4.6.6, A5E02430659B AG
147
Create generic I/O module
For certain control systems, you cannot use the EDS file provided by the ODVA. In these
cases, you must create a generic I/O module in the control system for the cyclic
communication.
Proceed as follows to create a generic I/O module:
1. In your control system, via "New module" create a new "I/O module", "Generic" type.
2. In the control system, enter the lengths for the process data for cyclic communication,
which you have selected in STARTER, r2067[0] (input), r2067[1] (output), for example:
Standard telegram 2/2.
3. In STARTER, set the same values for IP address, Subnet Mask, Default Gateway and the
Name of Station as in the control system (see Communication settings for Ethernet/IP
(Page 138))
You have created a generic I/O module for cyclic communication with the inverter.