Appendix
A.7 Application examples
Inverter with CU230P-2 Control Units
438 Operating Instructions, 11/2013, FW V4.6.6, A5E02430659B AG
STEP 7 program examples
A.7.3.1
Data exchange via the fieldbus - CU230
Data exchange via the fieldbus
Analog signals
The inverter always scales signals that are transferred via the fieldbus to a value of 4000
hex.
Table A- 10 Signal category and the associated scaling parameters
Control and status words consist of a high byte and a low byte. A SIMATIC control interprets
words differently than the inverter: The higher and lower-order bytes are interchanged when
they are transferred. See also the following program example.