3.4 System components for the Power Modules
Inverter with CU230P-2 Control Units
Operating Instructions, 11/2013, FW V4.6.6, A5E02430659B AG
33
3.4.2
Line reactor
The line reactor supports the overvoltage protection, smoothes
the
harmonics in the line supply and bridges commutation dips.
For the Power Modules subsequently listed, a line reactor is
suitable in order to dampen the specified effects.
Adjacent examples of line reactors.
for
PM240
for PM240-2
NOTICE
Damage to the inverter as a result of a missing line reactor
Depending on the Power Module and line supply, if a line reactors is not used, this can
result in damage to the inverter and other components in the electrical plant or system.
PM240 or PM240-2:
Install a line reactor if the relative short-circuit voltage of the line supply is below 1%
PM330:
You must always install a line reactor.
Line reactors for PM240
Power Module 6SL3224-…
Power
Line reactor
FSA
…0BE13-7UA0, …0BE15-5UA0
0.37 kW0.55 kW
6SE6400-3CC00-2AD3
…0BE17-5UA0, …0BE21-1UA0
0.75 kW1.1 kW
6SE6400-3CC00-4AD3
…0BE21-5UA0
1.5 kW
6SE6400-3CC00-6AD3
FSB
…0BE22-2A0, …0BE23-0A0
2.2 kW3.0 kW
6SL3203-0CD21-0AA0
…0BE24-0A0
4.0 kW
6SL3203-0CD21-4AA0
FSC
…0BE25-5A0, …0BE27-5A0
7.5 kW11.0 kW
6SL3203-0CD22-2AA0
…0BE31-1A0
15.0 kW
6SL3203-0CD23-5AA0
FSD
…0BE31-5A0, …0BE31-8A0
18.5 kW22 kW
6SL3203-0CJ24-5AA0
…0BE32-2A0
30 kW
6SL3203-0CD25-3AA0
FSE
…0BE33-0A0, …0BE33-7A0
37 kW45 kW
6SL3203-0CJ28-6AA0
FSF
…0BE34-5A0, …0BE35-5A0
55 kW75 kW
6SE6400-3CC11-2FD0
…0BE37-5A0
90 kW
6SE6400-3CC11-7FD0
…0BE38-8UA0 110 kW
132 kW
6SL3000-0CE32-3AA0
…0BE41-1UA0
6SL3000-0CE32-8AA0
FSGX …0XE41-3UA0 160 kW 6SL3000-0CE33-3AA0
…0XE41-6UA0, …0XE42-0UA0
200 kW250 kW
6SL3000-0CE35-1AA0