EasyManua.ls Logo

Siemens SINAMICS G120 - Analog Input as Setpoint Source; Specifying the Motor Speed Via the Fieldbus

Siemens SINAMICS G120
456 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Setting functions
8.3 Setpoints
Inverter with CU230P-2 Control Units
Operating Instructions, 11/2013, FW V4.6.6, A5E02430659B AG
239
8.3.1
Analog input as setpoint source
Interconnecting an analog input
If you have selected a pre-assignment without a function of the analog input, then you must
interconnect the parameter of the main setpoint with an analog input.
Figure 8-12 Example: Analog input 0 as setpoint source
Table 8- 7 Setting with analog input 0 as setpoint source
Parameter
Remark
p1070 = 755[0]
Main setpoint
Interconnect the main setpoint with analog input 0
p1075 = 755[0]
Additional setpoint
Interconnect the additional setpoint with analog input 0
You must adapt the analog input to the connected signal, e.g. ± 10 V or 4 … 20 mA. You will
find additional information in the section: Analog inputs (Page 98).
8.3.2
Specifying the motor speed via the fieldbus
If you enter the setpoint via a fieldbus, you must connect the converter to a higher-level
control. For further information, see Section Configuring the fieldbus (Page 107).
Interconnecting the fieldbus with the main setpoint
Figure 8-13 Fieldbus as setpoint source
Most standard telegrams receive the speed setpoint as a second process data PZD2.

Table of Contents

Other manuals for Siemens SINAMICS G120

Related product manuals