Technical data
12.2 Technical data, Power Modules
Inverter with CU230P-2 Control Units
Operating Instructions, 11/2013, FW V4.6.6, A5E02430659B AG
385
Power dependent data, PM230, IP55
Table 12- 12 PM230, IP55, Frame Sizes A, 3 AC 380 V … 480 V
Order No. - Filtered, Class A
Order No. - Filtered, Class B
Rated / LO power
Rated / LO input current
Rated / LO Output current
0.37 kW
1.3 A
0.55 kW
1.8 A
0.75 kW
2.3 A
HO power
HO input current
0.25 kW
0.9 A
0.37 kW
1.3 A
0.55 kW
1.8 A
Fuse according to IEC
3NA3803
3NA3803
3NA3803
Required cooling air flow
Cross section of line and motor cable 1 … 2.5 mm
2
1 … 2.5 mm
2
1 … 2.5 mm
2
Tightening torque for line and motor cable
Table 12- 13 PM230, IP55, Frame Sizes A, 3 AC 380 V … 480 V
Order No. - Filtered, Class A
Order No. - Filtered, Class B
Rated / LO power
Rated / LO input current
Rated / LO Output current
1.1 kW
3.2 A
3.1 A
1.5 kW
4.2 A
4.1 A
2.2 kW
6.1 A
5.9 A
HO power
HO input current
HO output current
0.75 kW
2.3 A
2.2 A
1.1 kW
3.2 A
3.1 A
1.5 kW
4.2 A
4.1 A
Fuse according to IEC
3NA3803
3NA3803
3NA3803
Required cooling air flow
Cross section of line and motor cable 1 … 2.5 mm
2
1 … 2.5 mm
2
1 … 2.5 mm
2
Tightening torque for line and motor cable