Configuring the fieldbus
7.3 PROFIdrive profile for PROFIBUS and PROFINET
Inverter with CU230P-2 Control Units
Operating Instructions, 11/2013, FW V4.6.6, A5E02430659B AG
121
Control and status word 3
The control and status words fulfill the specifications of PROFIdrive profile version 4.1 for the
"closed-loop speed controlled" mode.
Control word 3 has the following default assignment. You can change the signal
interconnection.
Signal interconnection
in the inverter
1)
Selects up to 16 different fixed setpoints.
Changes over between settings for
different motors (drive data sets).
Technology controller enable
Enable or inhibit speed controller droop.
12
Changes over the control mode for vector
control.
p1501[0] = r2093.12
Closed-loop speed control active
13
-- p2106[0] = r2093.13
External fault is active (F07860)
15 1 CDS bit 1 Changes over between settings for
different operation interfaces (command
data sets).
p0811[0] = r2093.15
If you switch from telegram 350 to a different one, then the inverter sets all interconnections p1020, … to "0".