Technical data
12.2 Technical data, Power Modules
Inverter with CU230P-2 Control Units
396 Operating Instructions, 11/2013, FW V4.6.6, A5E02430659B AG
380 V ... 480 V 3-ph. AC ± 10%
0 V 3-ph. AC … input voltage x 0.95 (max.)
0 … 650 Hz, depending on the control mode
0.7 without line reactor; 0.85 with line reactor
Uk ≥ 1%, a line reactor is required for lower values
Less than the input current
Pulse frequency (factory
setting)
4 kHz
The pulse frequency can be increased in 2 kHz steps. An increase in the pulse frequency
results in a lower output current.
Electromagnetic
Devices with filters in compliance with EN 61800-3: 2004 are suitable for Category C2
environments. For details, see the Hardware Installation Manual, Appendix A2.
DC braking, compound braking, dynamic braking with integrated braking chopper
Degree of protection IP20 built-in units
IP20 when mounted in a control cabinet
IP54 on the control cabinet wall
Operating temperature LO without derating:
HO without derating:
0 °C … +40 °C
0 °C … +50 °C
For details, see the Hardware
Installation Manual.
-40 °C … +70 °C (-40 °F … 158 °F)
< 95% - condensation not permissible
Protected according to pollution degree 2 to EN 61800-5-1: 2007
Environmental requirements Protected against damaging chemical substances according to environmental class 3C2 to
Shock and vibration
• Long-term storage in the transport packaging according to Class 1M2 to EN 60721-3-1:
1997
• Transport in the transport packaging according to Class 2M3 to EN 60721-3-2: 1997
• Vibration during operation according to Class 3M2 to EN 60721-3-3: 1995
Installation altitude without derating:
up to 1000 m above sea level
up to 4000 m above sea level
For details, see the Hardware
Standards UL, cUL, CE, C-tick, SEMI F47
The drive only satisfies the UL requirements when UL-certified fuses are used.