EasyManua.ls Logo

Siemens SINAMICS G120 - Two-Wire Control: Method 1

Siemens SINAMICS G120
456 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Setting functions
8.2 Inverter control
Inverter with CU230P-2 Control Units
230 Operating Instructions, 11/2013, FW V4.6.6, A5E02430659B AG
8.2.2
Two-wire control: method 1
You switch the motor on and off using a control command (ON/OFF1) while the other control
command reverses the motor direction of rotation.
Figure 8-3 Two-wire control, method 1
Table 8- 2 Function table
ON/OFF1
Reversing
Function
0
0
OFF1: The motor stops.
0
1
OFF1: The motor stops.
1
0
ON: Clockwise motor rotation.
1
1
ON: Counter-clockwise motor rotation.
Parameter
Description
p0015 = 12
Macro drive unit
(factory setting for inverters without PROFINET or
PROFIBUS interface)
Controlling the motor using the digital inputs
of the inverter:
DI 0
DI 1
ON/OFF1
Reversing
Advanced setting
Interconnecting control commands with digital inputs of your choice (DI x).
p0840[0n] = 722.x
BI: ON/OFF1 (ON/OFF1)
p1113[0n] = 722.x
BI: Setpoint inversion (reversing)
Example
p0840 = 722.3 DI 3: ON/OFF1
Also see section Digital inputs (Page 94).

Table of Contents