Technical data
12.2 Technical data, Power Modules
Inverter with CU230P-2 Control Units
Operating Instructions, 11/2013, FW V4.6.6, A5E02430659B AG
401
380 V ... 480 V 3-ph. AC ±10%
0 V 3-ph. AC … input voltage x 0.87 (max.)
Less than the input current
Pulse frequency (factory
setting)
4 kHz
The pulse frequency can be increased up to 16 kHz in 2 kHz steps. An increase in the pulse
frequency results in a lower output current.
Electromagnetic
The devices in compliance with EN 61800-3: 2004 are suitable for Category C1 and C2
environments. For details, see the Hardware Installation Manual, Appendix A2
DC braking, energy recovery (up to 100% of the output power)
Operating temperature LO without derating:
HO without derating:
0 °C … +40 °C
0 °C … +50 °C
For details, see the Hardware
Installation Manual.
< 95% - condensation not permissible
Protected according to pollution degree 2 to EN 61800-5-1: 2007
Environmental requirements Protected against damaging chemical substances according to environmental class 3C2 to
Shock and vibration
• Long-term storage in the transport packaging according to Class 1M2 to EN 60721-3-1:
1997
• Transport in the transport packaging according to Class 2M3 to EN 60721-3-2: 1997
• Vibration during operation according to Class 3M2 to EN 60721-3-3: 1995
Installation altitude without derating:
up to 1000 m above sea level
up to 4000 m above sea level
For details, see the Hardware
Standards UL, CE, CE, SEMI F47
The drive only satisfies the UL requirements when UL-certified fuses are used.