Configuring the fieldbus
7.3 PROFIdrive profile for PROFIBUS and PROFINET
Inverter with CU230P-2 Control Units
134 Operating Instructions, 11/2013, FW V4.6.6, A5E02430659B AG
Drive object does not exist (access to a drive object that does not exist)
No change access for a controller that is enabled.
Change request is only possible when the motor is being commissioned (p0010 = 3).
Change request is only possible when the power unit is being commissioned (p0010 = 2).
Change request is only possible for quick commissioning (basic commissioning) (p0010 = 1).
Change request is only possible if the inverter is ready (p0010 = 0).
Change request is only possible for a parameter reset (restore to factory setting) (p0010 = 30).
Change request possible only during commissioning of the safety functions (p0010 = 95).
Change request is only possible when a technological application/unit is being commissioned (p0010 = 5).
Change request is only possible in a commissioning state (p0010 ≠ 0).
Change request is not possible for internal reasons (p0010 = 29).
Change request is not possible at download.
Change request is not possible at download.
Transfer of the control authority (master) is inhibited by BI: p0806.
83 hex
Desired interconnection is not possible
(the connector output does not supply a float value although the
connector input requires a float value)
84 hex
Inverter does not accept a change request
(inverter is busy with internal calculations. See parameter r3996 in
the inverter List Manual. See also Section:
Manuals for your inverter (Page 446))
No access methods defined.
86 hex
Write access only during commissioning of the data records (p0010 = 15)
(operating status of the inverter
prevents a parameter change.)
Know-how protection active, access locked
C8 hex
Change request below the currently valid limit
(change request to a value that lies within the "absolute" limits,
but is however below the currently valid lower limit)
Change request above the currently valid limit (example: a parameter value is too large for the inverter power)
Change request not permitted (change is not permitted as the access code is not available)
"Reading and writing parameters acyclically" application example
See: (http://support.automation.siemens.com/WW/view/en/29157692).